8.3.5 Fire Pumps Systems

Fire Pump Assembly

Assembly to include Single-Stage, Horizontally or Vertically Mounted, Split-Case Fire Pump, Multi-stage, centrifugal Jockey Pump, Fire Pump Controller and all required accessories and specialties, including test header manifold, pressure gauges and relief valve.

Room Requirements

Room to be properly sized to allow proper service and maintenance of system, including proper clearance for all electrical and alarm panels. Room to be placed as close to point of water service entry as possible. Room to be a minimum 2 hour fire rating. Room requires a direct, unobstructed path to the exterior.

Controls

To comply with UL 218 and NFPA 20, assembly to have a free standing controller with integrated automatic transfer switch, starter and all required indicator lights.