Top of Page
Main

4.10 Generators

Shall be provided or replaced only as required by code. If a new generator is to be placed indoors, provide proper air intake/heat rejection louvers and flue discharge for the Generator. Verify the flue discharge and natural gas regulator vents are proper distance from any air intake or operable window per CBC. Intake and heat rejection damper actuators shall be hardwired to generator. Provide NO2 room sensor for diesel units, CO sensor for natural gas units.